Sales line+44 (0)1844 202101
Lines open Mon-Fri 9am-5pm

Cardinal iMDU12 S/D MDU Range

  • iMDU12B-S - single input
    iMDU12B-S - single input
  • iMDU12B-D - dual input
    iMDU12B-D - dual input
Cardinal iMDU12 S/D MDU Range
PN - 104756
£856.08(ex vat) / each
Qty Price
1-4£856.08 (ex vat)
5-9£836.01 (ex vat)
10+£836.01 (ex vat)

iMDU12B-S
Intelligent MDU: 12 outputs, single input, power monitoring, SNMP

A single input MDU with 12 independent outputs. It can be configured to send SNMP traps and email alarms when faults occur, including loss of input mains power and blown fuses. The unit includes remote power monitoring for optimising operational efficiency and early detection of faults within a rack, and an error log to record trends on equipment failure.

iMDU12B-D
Intelligent MDU: 12 outputs, dual input, power monitoring, SNMP

A dual input MDU with 12 independent outputs. If input 1 fails, the unit automatically connects input 2 to the 12 outputs. It can be configured to send SNMP traps and email alarms when faults occur, including loss of input mains power and blown fuses. The unit includes remote power monitoring for optimising operational efficiency and early detection of faults within a rack, and an error log to record trends on equipment failure. Automatic power shedding. If a back up power supply is selected, it may be necessary to switch off non-critical equipment by shedding a number of MDU outputs. Power shedding is configured for automatic operation in the MDU configuration page. High inrush current protection Both single and dual input versions are designed for use with equipment that has modern switch mode PSU’s that can exhibit high inrush currents. Individually switched outputs are rated to 60A inrush and the dual input changeover version has an inrush limiting circuit that restrictsthe current at switch on to 40A. 

Sequential power on/off. All outlets are individually switched enabling the user to control and set sequential switching, to prevent an excessive current surge on start-up and an orderly power-down when shedding outputs.

 Fail-safe. As standard the MDU outputs will switch off in the event of failure of the internal control system. Ordering the fail-safe option enables the outputs to remain on if the internal control system fails and the unit will revert to a conventional MDU.

Power management. The Cardinal range of MDUs include remote power monitoring for optimising operational efficiency and early detection of faults within a rack.

  • Power 
  • Input voltage 
  • Energy (KWh) 
  • Input current
  • Power factor

Network interface. The dB Cardinal intelligent mains distribution unit provides fully featured web and SNMP interfaces giving easy access to sophisticated remote control and configuration facilities. On loss of mains input large capacitors sustain the microcontroller for approximately ten seconds. This is long enough to record the fault and send SNMP traps to alert the management system.

Email alerts. The Cardinal range can be configured to provide email alerts for various conditions including; loss of input mains power, blown fuses and output status changing (i.e. relay on or off).

Logging. As well as error logging the MDU records five days of the peak and minimum values of certain parameters.

IP reset. An optional controller reset button can be added which enables the iMDU internal control system to be reset without interrupting any of the MDU outputs

Temperature and humidity sensing. An optional remote temperature and humidity sensor can be added for monitoring the temperature and humidity at any position within the equipment bay.

General purpose inputs. Each MDU includes 16 general purpose inputs for connection of alarms from other equipment. These alarms can be reportedin the same way as those for the MDU.

Input

  • Connector: 1 or 2 Neutrik Powercon inlets (depending on model type)
  • Voltage: 230V +/- 10%
  • LEDs: Single I/P; Supply LED (green)
    Dual I/P; Supply Active / Available LEDs per I/P (green) 

Outputs

  • Connector: 12 x IEC sockets on the rear panel
  • Individual fuse rating: 6A per output
  • Total load: Up to 12A at 230V
  • LEDs: 2 per output for “on/off” (green) and “fuse blown” (red)

Inrush Current Protection

  • Output: Up to 60A max per output
  • Input: Up to 200A at switch on 

Temp & Humidity Sensor

  • Temp range: -20 to +80 degrees
  • Temp accuracy: +/- 2 degrees
  • Humidity range: 5 to 95%
  • Humidity accuracy: 5%

Physical

  • Height:1RU bay mounted unit
  • Width: 483mm (standard 19 inch rack)
  • Depth: 380mm (including tie bar)
  • Switch: Front panel switch is also a thermal over-current circuit breaker
  • Tiebar: At the rear for cable retention
  • Weight: 2.9kg (single input version)

Environmental

  • Operational temp: 5 to 40 deg C, non condensing
  • Operational humidity: Up to 85% relative humidity

Control/monitoring

  • Network: Ethernet RJ45, 10/100baseT for SNMP interface and web configuration and monitoring via browser
  • Serial: RS232 via 6 way Modular Jack
  • GPIO: 27 way high density ‘D’ type. 16 inputs and 2 dry contact outputs